How to Install KBG and JDG Conduit: Cutting, Joining, Bending and Fixing

Created on 11.12

How to Install KBG and JDG Conduit: Cutting, Joining, Bending and Fixing

KBG and JDG are thin-wall galvanized steel conduits installed in the same order: check the parts, cut and deburr the tube, join it, bend it where needed, fix it to the structure, and check continuity before pulling cable. The main difference is the joint: KBG is joined with snap-press (compression) fittings, and JDG with set-screw fittings. This guide walks through each step and the mistakes that cause problems later. Always follow your project specification and the applicable local electrical code for spacing, bending limits and grounding.

Step 1: Check the Parts Before You Start

KBG and JDG Galvanized Steel Conduit Pipes and Matching Fittings

Step 2: Cut and Deburr

  1. Measure the run from box to box, allowing for the depth the tube enters each fitting.
  2. Cut square, using a pipe cutter or a fine-tooth saw. A crooked cut makes the joint sit badly.
  3. Remove burrs from the inside and outside of the cut end. A sharp inner edge can damage cable insulation during pulling.
  4. Touch up the bare cut end with a suitable zinc-rich or anti-rust coating where the project requires it, because cutting exposes bare steel.
Cutting and Deburring Galvanized Steel Conduit Pipes for Electrical Installation

Step 3: Join the Conduit

Item
KBG (snap-press)
JDG (set-screw)
Joint style
Tube is pushed into the fitting and fixed by pressing with a tool
Tube is pushed into the fitting and fixed by tightening screws
Tube must be
Fully inserted to the stop, with a clean, deburred end
Fully inserted to the stop, with a clean, deburred end
Key check
The press is complete and the tube cannot be pulled out by hand
Screws are tight and the tube cannot be pulled out by hand
Common mistake
Tube not fully inserted before pressing
Screws left loose, or over-tightened until the tube deforms
Whichever type you use, the joint should hold the tube firmly and give a
KBG Snap Press and JDG Set Screw Conduit Joining and Bending
continuous metal path from one tube to the next. Follow the fitting maker's instructions for the tool and tightening.

Step 4: Bend Where Needed

  • Use a bending tool made for the tube size. Bending over a knee, or by hand without a tool, tends to flatten the tube.
  • Keep the bend radius within the limit given by your specification or local code. A tighter bend makes pulling cable harder and can kink the tube.
  • Check that the bend is smooth and the tube has not flattened. A flattened section should be replaced.
  • Where a run needs many bends, consider a pull box or a fitting instead of one more bend. The number of bends allowed between pull points is set by code.

Step 5: Fix the Conduit in Place

  • Use clips, straps or clamps that fit the conduit outer diameter and suit the surface: concrete, brick, steel or a support channel.
  • Fix the tube close to each box, coupling and bend, and then along straight runs at the spacing your specification requires. Spacing values come from the project and local code, not from this article.
  • Do not fix a clip so tightly that it dents the tube, and do not leave long unsupported spans.
  • Where conduit crosses an expansion joint or meets equipment that moves, allow for movement as the specification directs.
  • Where conduit is concealed in concrete, fix it to the formwork or reinforcement so it does not move during the pour, and keep joints closed so concrete cannot enter.

Step 6: Terminate at Boxes

  1. Use the connector that matches the tube type and the box knock-out.
  2. Fit a bushing or locknut where the design calls for one, so the cable does not rub on a sharp edge.
  3. Seal unused knock-outs and keep the tube end square to the box.

Step 7: Check Continuity Before Pulling Cable

Metal conduit is often used as part of the bonding path, so every joint matters. Before pulling cable, check that each joint is tight and that every box and fitting is bonded as the design requires. Where a ground clamp or separate earth conductor is specified, install it as drawn, and make sure paint or dirt is not left between metal surfaces that must make contact. Measurement values and methods should follow your project requirements.
Galvanized Electrical Conduit Installation with Pipe Clips and Junction Boxes

Pre-Pull Checklist

Check
Done
Conduit and fittings are the same system (KBG or JDG)
☐
Cut ends are square and deburred
☐
Cut ends are touched up where required
☐
Every joint is fully inserted and pressed or tightened
☐
Bends are smooth, not flattened, within the radius limit
☐
Fixing points and spacing follow the specification
☐
Bushings or locknuts are fitted at boxes
☐
Bonding and ground connections are in place
☐
Runs are clear inside, with no blockage or burrs
☐

Common Mistakes

  • Mixing KBG and JDG parts.
  • Tube not fully inserted.
  • Skipping deburring.
  • Bending without a tool.
  • Over-tightening clips or screws.
  • Leaving cut ends bare in damp places.
  • Too few fixing points.

Conclusion

Good conduit installation is mostly careful basics: matched parts, square deburred cuts, fully seated joints, smooth bends, correct fixing, and a continuous metal path. Doing these in order saves rework when cable is pulled. For spacing, bending limits and earthing, use your project specification and local code, and choose a conduit and fittings range that matches the system you plan to build. If you are still choosing between types, read our guide to electrical conduit types.

FAQ

What is the main installation difference between KBG and JDG?

The joint. KBG is joined by pressing the fitting onto the tube, and JDG by tightening set screws. The other steps (cutting, deburring, bending, fixing) are very similar. Always use fittings made for the conduit type you have.

Do I need to touch up the cut ends of galvanized conduit?

Cutting exposes bare steel at the end. Whether and how to touch it up depends on the environment and your specification. In damp or outdoor locations it is good practice to treat it.

Can I bend KBG or JDG conduit by hand?

Small bends are done with a bending tool made for the size. Bending without a tool tends to flatten the tube. For larger sizes or many bends, use a fitting or a pull box. Follow the bend radius limit in your specification or local code.
Need KBG or JDG conduit and matching fittings for your project? Browse our galvanized conduit range or request a quote with your size list, conduit type and destination.

Copyright ©️ 2026, Shenzhen Wanan Industrial Co.,Ltd.. All Rights Reserved. Sitemap | Privacy Policy

Follow Us

Whatsapp.jpg

E-mail:

+86 18823394830

Tel:

abby@wananelectric.com

Whatsapp:

+86 18823394830

PRODUCT

Cable Tray

Metal Electrical Conduit

wanan-logo.png240.png

Room 17A01, Block 1, Yintai Building, No. 15 Huilong Road, Shengping Community, Longcheng Street, Longgang District, Shenzhen City,

Guangdong Province, China 

Shenzhen Wanan Industrial Co., Ltd. is a China-based manufacturer of Cable Tray Systems and GI Electrical Conduits, established in 2004.

We manufacture perforated cable trays, cable ladders, cable trunking, galvanized and ZAM cable trays, and EMT, IMC and rigid steel conduits. With 22+ years of manufacturing experience, we provide factory-direct supply, OEM/ODM customization, and technical support for EPC contractors, MEP contractors, distributors, and industrial projects worldwide.

Quick Links